Every scan-to-BIM quote meets the same question sooner or later: how detailed, and how accurate? The answer is two different measures, and mixing them up is a common source of disputes. This article explains LOD vs LOA, how they work together, and how to write them into a scope your client understands.

A model can be very detailed but inaccurate, or very simple but accurate. That is why a scope needs both.
LOD is most often defined with the BIMForum Level of Development Specification. In short:
For existing buildings, most scan-to-BIM projects deliver LOD 200 to 300 for architecture and structure. MEP is often lower because many systems are hidden in walls and ceilings and cannot be scanned.
LOA is defined in the USIBD Level of Accuracy Specification. It gives tolerance bands, usually stated at a 95% confidence level:
| LOA | Tolerance range |
|---|---|
| LOA10 | larger than 50 mm (user defined) |
| LOA20 | 15 mm to 50 mm |
| LOA30 | 5 mm to 15 mm |
| LOA40 | 1 mm to 5 mm |
| LOA50 | 0 mm to 1 mm |
The specification also separates measured accuracy (how good the scan data is) from represented accuracy (how close the model is to that data). A scanner can measure to a few millimetres, but a modeler who draws a perfectly straight wall over a wall that leans 20 mm still delivers LOA20 for that element.
Think of a table where each element group gets both values:
This is far clearer than "LOD 300 model", which says nothing about tolerance, and it shows the client where the cost goes: tighter LOA means more time per element.
A short scope section prevents most arguments at handover:
LOA is only meaningful if you can show it. Before delivery, compare the model with the point cloud and keep the result as part of the handover. Deviation Check colors every scan point by its distance to the model and lists the elements outside your tolerance, so you can fix them before the client finds them.
For surfaces that are not flat, such as uneven slabs and terrain, measuring points directly from the scan keeps the represented accuracy high: see Floor By Points and Topo By Points.
Clear LOD and LOA make quoting and checking easier. Read the full scan to BIM workflow in Revit, or keep your delivered model tidy with practical Revit naming conventions.